产品信息:MS2500G2-25E
软件信息:V1.5.12T04P02_G03
问题现象:设备日志以及GUI上只有DSU-1:2:1(DSU2625)的 EP2温度恢复正常打印,之前对应EP没有温度告警打印。
2.1日志分析
1、查看odsp.log文件,找到DSU-1:2:1 EP2温度恢复正常打印的时间点:
2023-03-08:11:43:15:0xb00001:SP2:DISK:Info:The temperature of EP2 in DSU-1:2 :1 becomes normal.
2、通过odsp.log中的时间点找到messages文件前后的日志打印:
Mar 8 11:38:15 00-b3-42-03-90-38 dsu_polling: ODSP:MSG:DISK: The temperature of DSU-1:2:1's EP2 is unsupported. Mar 8 11:38:15 00-b3-42-03-90-38 dsu_polling: ODSP:MSG:DISK: The temperature of DSU-1:2:1's EP2 is unsupported.--------------EP访问温度传感器失败 。。。 Mar 8 11:43:15 00-b3-42-03-90-38 dsu_polling: ODSP:MSG:DISK: The temperature of EP2 in DSU-1:2:1 becomes normal.----------------------EP访问温度传感器成功 Mar 8 11:43:15 00-b3-42-03-90-38 dsu_polling: ODSP:MSG:LOG-EVENT: The temperature of EP2 in DSU-1:2:1 becomes normal. Mar 8 11:43:15 00-b3-42-03-90-38 eventd: --------------------evtname dsu_update Mar 8 11:43:15 00-b3-42-03-90-38 eventd: --------------------json {"ep_model": "DSU", "location": 16908289}
3.1问题原因及影响
问题原因:软件每隔5分钟会轮询获取DSU相关硬件状态信息,当轮询查询EP温度时出现温度传感器访问失败,但下次轮询时可正常获取到EP温度后就会打印温度becomes normal,根据目前情况研发暂未能定位EP温度传感器访问失败原因,该问题不影响设备功能及运行,计划在后续版本优化此类打印;
3.2解决方案
目前该问题主要出现在DSU2625设备上,该问题不影响设备功能及运行,研发计划在后续版本优化此类打印,同时内部会继续跟踪定位DSU2625的EP温度传感器访问失败原因
涉及软件版本:当前已发布的版本上都会存在此类打印,后续版本研发会优化此类打印;
涉及硬件型号:目前主要出现在DSU2625设备上。
该问题不影响设备功能及运行,现阶段现场可以先持续观察,待研发后续发布新版本优化此类告警后可考虑升级版本解决。